Question 510
At Baystone Energy Services, an OT security team is reviewing Fortinet-protected operational technology networks during a process safety change review. The issue observed is that a DNP3 control link is secured using only a source-IP allow rule without validating master versus outstation command direction. The correction must preserve correct alarm escalation and traceable operator ownership. Which observation would most directly demonstrate that the correction works?
Explanation
Correct Answer
For Baystone Energy Services, the decisive evidence is straightforward: A test with sanctioned telemetry succeeds while an unapproved command direction is rejected. That result matters because IP addresses alone do not express the approved DNP3 role and control operation boundaries. For Baystone Energy Services, the related corrective action is to inspect supported DNP3 application behavior and restrict traffic to the documented master-outstation workflow.
Incorrect Answers
This would be useful evidence for OPC UA security mode mismatch, where an OPC UA data exchange is allowed without evaluating endpoint certificate trust and security-mode requirements. It does not show that a test with sanctioned telemetry succeeds while an unapproved command direction is rejected. For Baystone Energy Services, the acceptance criterion must measure the stated OT-security outcome directly.
The test belongs to a different situation (Siemens S7 engineering protocol exposure), where a PLC engineering service is reachable from general office endpoints because the policy treats S7 traffic as ordinary TCP application access. It does not show that a test with sanctioned telemetry succeeds while an unapproved command direction is rejected. For Baystone Energy Services, the acceptance criterion must measure the stated OT-security outcome directly.
This observation checks Virtual patching for unpatchable PLC, where a vulnerable legacy controller cannot accept a firmware fix but remains reachable from a higher-risk manufacturing network. It does not show that a test with sanctioned telemetry succeeds while an unapproved command direction is rejected. For Baystone Energy Services, the acceptance criterion must measure the stated OT-security outcome directly.